Fuel Tank Coating & Liner
Interior Tank Coating for Petroleum Tanks
Choosing a high-quality and experienced team to provide you with your interior tank coating is essential. American Coating Technology uses the American Petroleum Institute Standard 652 for the lining of above-ground petroleum storage tanks.
Our Interior Tank Coating Process For Fuel Tanks
During our inspection of your tank, we will determine the extent of repairs necessary to meet the API 652 standard. We will then decide on the best blast cleaning system for surface preparation to match the requirements. We will determine the abrasive particles and technique necessary to remove mill scale, rust, corrosion, and previously applied coating to achieve an SSPC-SP10 near white metal blast with a 2 to 3-mil profile.
American Coating Technologies always controls the relative humidity during the blasting cycle and will apply a holding primer if necessary.
We will apply the first coat of our phenolic flexible epoxy coating at the rate of 10 to 12 mil thick. We then allow the coating to cure for a period of a minimum of 24 hours and then apply a second coat of our epoxy at the rate of 10 to 12 mil thick for a minimum of 20 mils thick.
We always subject the entire area to a Discontinuity (Holiday) Test using 25,000-volt test equipment. We guarantee our system for a period of five years for the use of tank protection from crude oil, refined petroleum, unleaded gasoline, MTBE, aromatic solvents, and most octane-boosted blending fuel stocks.
Get Started Today with An Interior Tank Coating from American Coating Technologies
Hundreds of customers depend on American Coating Technologies each year to provide on-time installations, with the highest quality, at the best value. For additional information about our interior tank coating services, contact us today!
We serve clients across Ohio, Pennsylvania, New Jersey, New York, Massachusetts, Connecticut, Vermont, and New Hampshire, providing top-quality, durable, and reliable tank lining solutions.